9410 Regenerative Grid Simulator

Regenerative Grid Simulator for Testing of Grid-Tied Inverters, V2G, & Other AC Power Products

The 9410 is a four-quadrant (bi-directional) AC/DC source with selectable phase outputs, a built-in waveform-digitizing measurement system and robust line disturbance creation tools. When used in the regenerative (sink) mode, it sends returned power back to the facility mains rather than being dissipated as heat. The most frequent application of the 9410 is use as a grid simulator for testing PV inverters and other grid-tied products for compliance to industry standards.

  • 8 models – 4kW/10.5kVA to 96kW/252kVA
  • Output AC Voltage Ranges – 175, 350VRMS L-N
  • Output DC Voltage – 200, 400VDC
  • Output Frequency – DC, 30 to 100Hz
  • Programmable 1, 2 or 3-Phase modes
  • Full 4 quadrant AC source operation
  • High resolution waveform capture on all V & I
  • Sink power regenerated back to facility
  • 9” Touch-Panel user interface
  • SCPI programming & NI LabVIEW drivers

Advantages

  • Bi-directional AC – Inverter testing & μgrid simulation
  • More reactive power per kW
  • Simplifies automated test stand development
    – Software selectable 1, 2, or 3 Phase operation
    – Isolated digital inputs & outputs
    – Built-in SW watchdog & safety limits
  • Software tools to shorten test development time
    – PC-based tools & NI certified drivers
    – NI certified LabVIEW & IVI-C/IVI-COM drivers
    – Optional: Enerchron® test sequencer

Benefits

  • Regenerative, returns greater than 85% of power to the facility, which provides significant electrical savings.
  • Field upgradeable to higher power
  • Fully emulate any utility/grid condition
  • Simulate non-ideal Phase phase angles (A-B & A-C)

HRegenerative Grid Simulator Specifications – Model 941

 

Model Number 9410-4 9410-8 9410-12 9410-24 9410-36 9410-48 9410-72 9410-96
AC Output Ratings
Phases/Output Channels 1 1 or 2 1,2, or 3
Power, Max (1Φ or 3Φ) 4kW/
10.5kVA
8kW/
21kVA
12kW/
24kVA
24kW/
48kVA
36kW/
94.5kVA
48kW/
96kVA
72kW/
144kVA
96kW/
192kVA
Current Ranges (RMS per Φ) 6, 30 A/Φ 6, 30 A/Φ 6, 30 A/Φ 12, 60 A/Φ 18, 90 A/Φ 24, 120 A/Φ 36, 180 A/Φ 48, 240 A/Φ
Current Ranges (RMS 1Φ) 6, 30A 12, 60A 18, 90A 36, 180A 54, 270A 72, 360A 108, 540A 144, 720A
Peak Current 3 X Max RMS
Frequency 30-100Hz (option up to 880Hz)
Voltage Ranges, L-N 175, 350V (Split Phase 250V Max)
  Accuracy 0.2% Set + 0.2% Rng
  Resolution 0.005% Rng
  Distortion (THD) <1% @ 50/60Hz (Full power into resistive load at 480 VRMS (L-L))
  Response Rate 1V/µS (10% to 90% measured at 90 degree turn-on into resistive load)
  Custom Waveforms Sine, n-Step Sine, Triangle, Clipped-Sine, Arbitrary (user defined)
  Phase Angle Control 0 to 359 degrees/1 degree resolution
DC Output Ratings
Power Max (1ch or 3ch) 4kW 8kW 12kW 24kW 36kW 48kW 72kW 96kW
Current Ranges (Per Ch.) 6, 30A/CH 6, 30A/CH 6, 30A/CH 12, 60A/CH 18, 90A/CH 24, 120A/CH 36, 180A/CH 48, 240A/CH
Current Ranges (Per System) 6, 30A 12, 60A 18, 90A 36, 180A 54, 270A 72, 360A 108, 540A 144, 720A
Voltage Ranges 200, 400 VDC
  Accuracy 0.2% Set + 0.2% Range
  Ripple <800mV RMS
AC & DC Measurements
Peak Voltage 250, 500V
  Accuracy (AC RMS) 0.1% Rdg + 0.06% Rng
  Accuracy (DC) 0.1% Rdg + 0.1% Rng
  Accuracy (Peak) 0.5% Rdg + 0.2% Rng
  Resolution 0.005% Rng
Peak Current (per Ch.) 20, 100A 20, 100A 20, 100A 40, 200A 60, 300A 80, 400A 120, 600A 180, 800A
  Accuracy (AC RMS) 0.2% Rdg + 0.06% Rng
  Accuracy (DC) 0.2% Rdg + 0.06% Rng
  Accuracy (Peak) 0.5% Rdg + 0.2% Rng
  Resolution 0.005% Rng
Peak Power V Range x I Range
  Accuracy (AC RMS) 0.2% Rdg + 0.06% Rng
  Resolution 0.005% Rng
Additional Measurements Energy (Ah, kWh, kVAh), AC Crest Factor, AC Power Factor, Waveform Capture
Physical
Enclosure Chassis Chassis Chassis Cabinet Cabinet Cabinet Cabinet (2) Cabinet (2)
Size (HxWxD) 400x483x610 400x483x610 400x483x610 1244x584x762 1549x584x762 1981x584x762 1981x1168x762 1981x1168x762
Weight 105lbs/
48kg
120lbs/
54kg
135lbs/
61kg
370lbs/
168kg
505lbs/
229kg
855lbs/
388kg
1340lbs/
608kg
1610lbs/
730kg
* The above specifications show typical configurations. Contact NH Research, Inc. for more information on other model options or custom configurations.